c17560 d5e generator

QSK60 for Data Center Continuous (DCC) Rating

Frequency (Hz) 50, 60
Certification N/A

Overview:

Cummins® commercial generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for data center applications.

Design: 4 cycle, V-black, turbocharged and low temperature after-cooled

Bore: 158.8 mm (6.25 in)

Stroke: 190.0 mm (7.48 in)

Displacement: 60.2 L (3673 in3)

Cylinder block: Cast iron, 60° V 16 cylinder

Battery capacity: 2200 amps at ambient temperature 0 °F to 32 °F (-18 °C to 0 °C)

Battery charging alternator: 40 amps

Starting voltage: 24 volts, negative ground

Fuel system: Direct injection

Fuel filter: Triple element, spin on fuel filters with water separator

Air cleaner type: Dry replaceable element

Lube oil filter type(s): Four spin-on, combination full flow and bypass filters

Standard cooling system: 104 ºF (40 ºC) ambient radiator

Generator Model Hz Data Center Continuous kVA / kW Spec Sheet
C1760 D5e 50 1600 / 1280 SS17-CPGK-DC50
DQKAH 50 1825 / 1460 S-1645DC
C2000 D5e 50 1825 / 1460 SS17-CPGK-DC50
C2000 D5 50 1875 / 1500 SS17-CPGK-DC50
DQKAG 50 2000 / 1600 S-1645DC
DQKAD 60 2000 / 1600 S-1627DC
C2250 D5 50 2000 / 1600 SS17-CPGK-DC50
C2500 D5A 50 2250 / 1800 SS17-CPGK-DC50
DQKAJ 50 2250 / 1800 S-1645DC
C2000 D6 60 2281 / 1825 SS17-CPGK-DC60
DQKAE 60 2281 / 1825 S-1627DC
C2250 D6A 60 2500 / 2000 SS17-CPGK-DC60
DQKAF 60 2500 / 2000 S-1627DC
DQKAN 60 2813 / 2250

Data Center Continuous (DCC) - Applicable for supplying power continuously to a constant or varying electrical load for unlimited hours in a data center application.

Uptime Compliant - Meets the requirement of a Tier III and IV data center site by being rated to run for unlimited hours of operation when loaded to 'N' demand for the engine generator set.

Cummins heavy-duty engine - Rugged 4- cycle, industrial diesel delivers reliable power, low emissions and fast response to load changes.

Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.

Permanent Magnet Generator (PMG) - Offers enhanced motor starting and fault clearing short circuit capability.

Control system - The PowerCommand® digital control is standard equipment and provides total genset system integration including automatic remote starting/stopping,precise frequency and voltage regulation, alarm and status message display, AmpSentryTM protective relay, output metering and auto-shutdown at fault detection and NFPA 110 Level 1 compliance.

Cooling system - Standard and enhanced integral set-mounted radiator systems, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.

NFPA - The genset accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.

Warranty and service - Backed by a comprehensive warranty and worldwide distributor network.